Description

Refer to Diagnostic class (standard): 2

Reaction: D

For every change in topology (ring interruption or ring repair), the diagnostic message (alert) with the following DiagExtMsg is issued:

DiagExtMsg

Description

Top=1

Line port 1 (Ring was interrupted such that a device line is present at port 1)

Top=2

Line port 2 (Ring was interrupted such that a device line is present at port 2)

Top=3

Double line (Ring was interrupted such that one device line is present at port 1 and one device line is present at port 2)

Top=4

Ring (Ring interruption has been rectified. Ring has been repaired.)

Top=8

Invalid topology (Switchover not possible)