AutoRun

General

Type

ER

Devices supporting the parameter

PacDrive LMC x00C, PacDrive LMC x01C

Traceable:

Yes

Functional Description

Automatic program start after creating the control voltage.

NOTE: This parameter is a reset parameter (ER). Changes will take effect only after a reset of the controller. To save the values as initialization values after changing the value of the parameter via online change or in the application, the function FC_SysSaveParameter has to be called.

Presetting

The presetting for AutoRun = FALSE.

Commissioning

While preparing the application and during commissioning, AutoRun must be set to false.

Regular Machine Operation

 WARNING
UNINTENDED EQUIPMENT OPERATION
Use appropriate safety interlocks where personnel and/or equipment hazards exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

During regular machine operation the parameter AutoRun = TRUE. Otherwise the start of the application can only take place via Logic Builder.

Value

Data type

Meaning

no / 0

BOOL

No automatic program start

yes / 1

BOOL

Automatic program start after booting the PacDrive controller