8978 InverterEnableConfig invalid

Ext. Diagnosis = x(HW)!=y(Cfg)

The hardware configuration (HW) of the real device (Lexium 62 ILM Drive Module) does not match the set value of the parameter InverterEnableConfig (Cfg). x and y each are the corresponding ENUM value.

Example:

Ext. diagnosis = 1(HW)!=0(Cfg)

The optional module DIS1 is not connected to the Lexium 62 ILM, even though the parameter value of the InverterEnableConfig is off / 0. This means that the optional module should be connected.

Cause

Solution

-

  • Verify the parameter InverterEnableConfig. Adjust the parameter if necessary.