Conditions for UL Compliant Use

General

According to UL508C rules, direct measurement motor over temperature sensing is required. Therefore, connect the temperature sensor of the motor to connection CN11.

Fuses

Use class CC or class J fuses according to UL 248-4.

Maximum fuse for Lexium 52 to be connected upstream at 30 A.

Wiring

Use at least 60/75 °C (140/167 °F) copper conductors.

Three-Phase Devices

400/480 V three-phase devices may be operated at 480 Y / 277 Vac networks maximum.

Overvoltage Category

Use only in overvoltage category III or where the maximum available Rated Impulse Withstand Voltage Peak is equal or less than 4000 Volts.", or equivalent.

Short-Circuit Current Rating (SCCR)

Only connect the Lexium 52 Standalone Drive System to a mains supply network not exceeding the SCCR (Short Circuit Current Rating) from table below, or take appropriate measures according to UL 508A SB4 in the supply (feeder) circuit of the control cabinet to limit the short circuit current to a value below the least SCCR of those devices you are using from the following table:

Lexium 52 Standalone Drive System

Short-Circuit Current Rating(1)

Lexium 52

22 kA

(1)   Using Class CC or J fuses.

Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.

Line reactors according to UL 508 A (SB 4.2.1 Exception No. 1) are not required to have a short-circuit current rating (SCCR).